MAS Cables > | Mas Fireres Cables > Mas Fireres Cables > Conduit Wirings |
FR2C
CH-43 | CH-10 | |||
Remark: The colour of the product refer to sample
Product Ref | FR2C |
---|---|
Product Description | Mica/Glass Tape, Low Smoke Zero Halogen (LSOH) Insulated Non Sheathed Two-core Twisted Cables |
Standards | Circuit integrity under fire condition : a) IEC60331-21 (950oC, 3 hrs) b) BS6387 Cat C, W & Z c) EN50200 ( PH120) Flame propagation : IEC60332-1-2 Acid gas emission : IEC60754-1 & 2 smoke emission : IEC61034-2 |
Construction | 2 nos. of single-core fire resistant cable (FR1C) twisted together. (In short form: 2/C Cu/FR/LSOH) |
Voltage Rating | 600/1000 Volts |
Application | This cables are typical use in fire alarm system. To optimize its performance, the cables should be installed in metal conduits or cable trunking |
Standard Colour | Red & Black or Brown & Blue |
Current Carrying Capacity & Volt Drop | Current carrying capacity, volt drop & the other relevant derating factors are available upon request |
Max. Conductor Temperature | 90˚C |
No. of Core x Nominal Area of Conductor (mm2) | Conductor Class | Insulation Thickness (mm) | Mean Overall Diameter (mm) | Max. Conductor Resistance at 20℃ (Ω/km) | Min. Insulation Resistance at 90℃ (MΩ • km) | Calculated Cable Weight (kg/km) |
---|---|---|---|---|---|---|
2 x 1.0 | 2 | 0.7 | 9.1 +/- 0.8 | 18.1 | 0.011 | 40 |
2 x 1.5 | 2 | 0.7 | 9.6 +/- 0.9 | 12.1 | 0.01 | 46 |
2 x 2.5 | 2 | 0.8 | 10.5 +/- 1.0 | 7.41 | 0.009 | 70 |