Product Catalogue
MAS Cables > Prefabricated Branch Cables > Prefabricated Branch Cables

FZ-FR1CXL

         
         
         
         
Product Ref FZ-FR1CXL
Product Description Mica/Glass Tape with XLPE insulated and LSOH sheathed branch cables
Standards Construction for main & branch cables : IEC60502-1 Branch joint tested to comply with a) JCS376A & JISC2810 b) JG/T147 Circuit integrity under fire condition: a) IEC60331-21 (950oC, 3 hrs) b) BS6387 Cat. C, W & Z
Flame propagation: IEC60332-3-24
Acid gas emission : IEC60754-1 & 2
Low smoke emission : IEC61034-2
Construction Stranded plain annealed copper conductor, mica/glass with XLPE insulated and LSOH sheathed branch cables
Voltage Rating 600/1000 Volts
Application Design as riser mains in building power distribution and specially consider those instalations where the low emission of smoke & corrosive gases under fire conditions must be necessary for public safety and a fire situation may pose a major hazard & the maintenance of circuit integrity is a requirement.
Core Colour Brown, Blue, Grey or Black
Sheath Colour Black or other colours upon request
Current Carrying Capacity & Volt Drop Current carrying capacity, volt drop & the other relevant derating factors are available upon request
Nominal Area of Conductor (mm2) Conductor Class Insulation Thickness (mm) Sheath Thickness (mm) Mean Overall Diameter (mm) Max. Conductor Resistance at 20℃ (Ω/km) Calculated Cable Weight (kg/km)
25 2 0.9 1.4 12.6 0.727 302
35 2 0.9 1.4 14 0.524 403
50 2 1 1.4 16 0.387 554
70 2 1.1 1.4 18 0.268 752
95 2 1.1 1.5 20.5 0.193 997
120 2 1.2 1.5 22 0.153 1248
150 2 1.4 1.6 24 0.124 1550
185 2 1.6 1.6 27.5 0.0991 1902
240 2 1.7 1.7 30 0.0754 2443
300 2 1.8 1.8 33 0.0601 3025
400 2 2 1.9 36.5 0.047 4006
500 2 2.2 2 41 0.0366 4980
630 2 2.4 2.2 46 0.0283 6243
800 2 2.6 2.3 51.5 0.0221 7886

 

 